Galaxy Reader Wiring QRS

 

 

 

 

1.0 Wiegand Reader - Cable Specs & Wiring Pinout

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet. 

  • Reader will require separate power supply if the current draw is over 150 mA.

  • Ground the Drain-wire at one end only - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

  • 635-DRM Board (PN 20-0235-10)

     

635-DRM Terminals (Function)

Wiegand Reader

LED    (LED control line)

LED Control

D 1     (Data 1)

DATA 1

VDC    (+12 VDC)   ( for +5 VDC use Regulator PN 92-3001-05 )

VDC

GND    (Power Supply Ground)

GND

D 0    (Data 0)

DATA 0

 

2.0 ABA Reader - Cable Specs & Wiring Pinout

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet. 

  • Reader will require separate power supply if the current draw is over 150 mA.

  • Ground the Drain-wire at one end only  - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

  • 635-DRM Board (PN 20-0235-10)

     

635-DRM Terminals (Function)

ABA Reader

LED     (LED control line)

LED Control

D 1    (Data 1)

DATA 1

VDC    (+12 VDC)   ( for +5 VDC use Regulator PN 92-3001-05 )

VDC

GND    (Power Supply Ground)

GND

D 0    (Clock Data)

CLOCK

 

back to top

3.0 Biometric Reader - Cable Specs & Wiring Pinout

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet.

  • Cat-5e Ethernet cable for TCP/IP communication back to the server; max cable distance 300 feet.

  • Reader will require separate power supply if the current draw is over 150 mA.

  • Ground the Drain-wire at one end only - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs)

  • 635-DRM Board (Dual Reader Module) – PN 20-0235-10

  • See next section for information on IDEMIA Morpho Sigma Readers.

     

635-DRM Terminals (Function)

Wiegand Reader

LED    (LED control line)

LED Control

D 1    (Data 1)

DATA 1

VDC    (+12 VDC)   ( for +5 VDC use Regulator PN 92-3001-05 )

VDC

GND    (Power Supply Ground)

GND

D 0    (Data 0)

DATA 0

 

back to top

4.0 IDEMIA (Morpho) SIGMA Reader - Cable Specs & Wiring Pinout

  • 3-conductor, 20 - 24 AWG, overall shielded; non-stranded; max cable distance is 500 feet.

  • 2-conductor, 16 AWG for at +12vdc (18 AWG for +24vdc) for 500 feet distance. Reader draws 1A at 12v (0.5A at 24v).

  • Cat-5e Ethernet cable for TCP/IP communication back to the server; max cable distance 300 feet.

  • Separate power supply required (current draw is 1A). Must common reader's p.s. ground to controller ground.

  • Ground the drain-wire at one end only - land drain wire at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

  • 635-DRM Board (Dual Reader Module) – PN 20-0235-10

  • DRM Relay-2 is used to control Sigma “Wait for Panel Decision” for Voice/Prompt synchronization.

 

 

635-DRM Terminals (Function)

SIGMA Reader

LED    (LED control line)

 

D 1    (Data 1)

WIEG DATA 1

VDC    (use separate p.s. for reader power)

VDC (to separate p.s.)

GND    (common the reader p.s. ground to Controller ground)

GND (common to controller ground)

D 0    (Data 0)

WIEG DATA 0

 

 

635-DRM RELAY-2

SIGMA “Wait for Panel Decision”

COM    (must tie to ground of the reader’s power supply)

-  -

NO    (for voice/prompt control line)

LED1 

 

 

NOTES:

  • “Wait for Panel Decision”: connect Sigma LED1 to the ‘NO’ leg of Relay-2. The ‘COM’ leg of Relay-2 must be tied to DRM GND.

  • Set Relay-2 for Timed Mode (1 to 2 secs) and “Valid Unlock” checkbox must be "checked" in System Galaxy Reader Properties.

 

back to top

5.0 Invixium (IXM) Reader - Cable Specs & Wiring Pinout

  • 3-conductor, 20 - 24 AWG, overall shielded; non-stranded; max cable distance is 500 feet.

  • 2-conductor, 18 AWG for at +12vdc for 500 feet distance. Reader draws 1A at 12v.

  • Cat-5e Ethernet cable for TCP/IP communication back to the server; max cable distance 300 feet.

  • Separate power supply required (current draw is 1A). Must common reader's p.s. ground to the controller ground.

  • Ground the drain-wire at one end only - land drain wire at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

  • 635-DRM Board (Dual Reader Module) – PN 20-0235-10

  • 635-DRM Relay-2 is used to control Sigma “Wait for Panel Decision” for Voice/Prompt synchronization.

 

 

635-DRM Terminals (Function)

SIGMA Reader

LED    (LED control line)

ACP LED1 (used to control Voice Command)

D 1    (Data 1)

W DATA_OUT1

VDC    (use separate p.s. for reader power)

 

GND    (common the reader p.s. ground to Controller ground)

VIN – (GND) (bond to controller GND)

D 0    (Data 0)

W DATA_OUT0

   
 

VIN + (VDC) to separate power supply

 

VIN – (GND) to separate power supply

 

NOTES:

  • The IXM Reader must be configured to “follow panel decision” in the IXM-WEB software in reader configuration screen.

  • Galaxy controller must be set for Door Lock = Steady-High; Door Unlock = Steady-Low in the LED Options tab of the Loop/Cluster Properties screen.

 

back to top

6.0 Veridt Stealth Series FICAM Solution for Technologies Industry

  • 5-conductor 22 AWG overall shielded; max cable distance 500 feet

  • 2-conductor Twist pair, 22 AWG, max line distance 4000 feet (RS-485 Comm. for Mode/Factor Control)

  • A separate Power Supply is required (reader draws 400 mA at +12vdc).

  • Must common reader's power supply ground to controller ground.  

  • Ground the Drain-wire at one end only - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy recommendations).

  • Min. Board Requirement: 635-DSI Board (Dual Serial Interface)    – PN 20-0655-10   – for Mode/Factor Control

 

READER MODES/FACTORS

 

EWAC to 635 DRM Wiring Pinout

 

Mode 1 Card Only

 

EWAC Module

635 DRM

Mode 2 Card + Pin

 

GND

- - - - - - - -

GND

Mode 3 Card + Pin + Bio

 

D0

- - - - - - - -

D0

 

 

D1

- - - - - - - -

D1

 

 

I/O

- - - - - - - -

LED

 

 

NC

- - - - - - - -

Not Used

 

  1. Install System Galaxy (SG) software according to Galaxy documentation.

  2. Validate WEB API by using address: http://localhost:8000/swagger.

  3. Also verify the GCS DataLoader Service is running on the Galaxy Comm/Event Server.

  4. When you add the 635-Series Clusters into the SG Loop/Cluster Properties screen, do the following …

On the Advanced tab,

set the Card Data Mode droplist to
“Extended Card (256 Bits)”.

ADVANCED opts

On the LED Options tab, set LED States:

DOOR Locked = ‘Steady High’

DOOR Unlocked = ‘Steady Low’

LEDopts

 

  1. In the SG Reader Properties screen, configure the Reader Type field to ‘Standard Wiegand’.

  2. In the SG Access Group Properties screen, you must create the Access Groups you will need.

  3. In the SG Access Profile Properties screen, you must create 1 or more Access Profiles by assigning your access groups to the profile, based on your system needs.

  4. Install the Galaxy 635-series Controller hardware according to Galaxy documentation.

    • In the controller, be sure to enable Extended Card Mode (set to “yes” in lower case).
    • Be sure to configure the correct IP Address for the Event Server.
  5. Install the Technology Industries (TI) FICAM software per the manufacturer’s documentation.

  6. from the SG Cardholder screen perform a card lookup of the GOV. ID CARD to validate that it is correctly pushed from the TI FICAM Software into System Galaxy database.

  7. Install Veridt Reader and EWAC Module according to the manufacturer’s documentation.

  8. Connect the EWAC Module to the Galaxy Model 635 DRM (Dual Reader Module) using the wiring pinout in the table above. 

 

 

back to top

7.0 Veridt Stealth Series Readers (NON-FICAM)

  • 5-conductor 22 AWG overall shielded; max cable distance 500 feet.

  • 2-conductor Twist pair, 22 AWG, max line distance 4000 feet (RS-485 Comm. for Mode/Factor Control)

  • Separate Power Supply required (reader draws 400 mA at +12vdc). Common reader's power supply ground to controller ground.  

  • Ground the Drain-wire at one end only - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy recommendations).

  • Min. Board Requirement: 635-DRM Board (Dual Reader Module)    – PN 20-0235-10

  • Min. Board Requirement: 635-DSI Board (Dual Serial Interface)    – PN 20-0655-10  – for Mode/Factor Control

 

READER MODES/FACTORS

  • Mode 1 Card Only

  • Mode 2 Card + Pin

  • Mode 3 Card + Pin + Bio

 

 

635-DRM Terminals (Function)

Veridt Wiegand Reader

LED    (LED control line)

LED Control * required for correct operation

D 1    (Data 1)

DATA 1

VDC   (use separate p.s. for reader power)

VDC (to separate p.s.)

GND   (common Reader’s p.s. ground to Controller ground)

GND (common to controller ground)

D 0    (Data 0)

DATA 0

 

 

635-DSI Terminals / Function

Veridt Reader RS-485 Comm.

A +    RS-485 Data

Yellow Wire

B –    RS-485 Data

Blue Wire

 

 

NOTES:

  • DSI Section used for Mode/Factor Control must be set to “Veridt CAC Reader” in System Galaxy Serial Channel Properties.

  • LED Option must be set for Door Locked “Steady High” and Door Unlocked “Steady Low” in System Galaxy Loop Properties.

     

     

 

back to top

8.0 BridgePoint (NON-FICAM)

  • 5-conductor, 22 AWG, overall shielded max distance 200 Feet.  (or 500 feet if using 18 AWG).

  • 2-conductor- twisted pair, 22 AWG max cable distance 500 feet.  (for Mode/Factor Control).

  • Separate Power Supply required (reader draws 300 mA at +12VDC).  Must common reader's p.s. ground to controller ground.

  • Ground the Drain-wire at one end only - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy recommendations).

  • Min. Board Requirement: 635-DRM Board (Dual Reader Module) – PN 20-0235-10

  • DRM Relay-2 must be use for Mode/Factor Control. 

 

MODES/FACTORS:

  • Mode 1 Card Only (high)

  • Mode 2 Card + Pin (low)

 

 

635-DRM Terminals (Function)

BridgePoint Wiegand Reader

LED    (LED control line)

LED1

D 1    (Data 1)

WEG 1

VDC    (use separate p.s. for reader power)

VDC (to separate power supply)

GND    (common the Reader’s p.s. ground to the Controller ground)

GND (common to controller ground)

D 0    (Data 0)

WEG 0

 

 

635-DRM RELAY-2

BridgePoint Mode/Factor

COM    (must tie to the reader’s power supply ground)

-  -

NO    (to mode control line)

LED2 

 

 

NOTES:

  • Mode signal line High (unconnected) for 1-Factor Card Only.

  • Mode signal line Low (connected to ground) for 2-Factor Card + Pin.

  • Place a schedule on Relay-2 in System Galaxy Reader Properties - to alternate Mode/Factor.  

     

 

 

back to top

9.0 SCM Readers (NON-FICAM)

  • 5-conductor, 22 AWG, overall shielded max cable distance 500 feet.

  • 2-conductor- twisted pair, 22 AWG, max cable distance 500 feet (for Mode/Factor Control).

  • Separate Power Supply required (reader draws 300 mA at +12VDC). Must common reader P.S. ground to controller ground.  

  • Ground the Drain-wire at one end only  - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs)

  • Min. Board Requirement: 635-DRM Board (Dual Reader Module) – PN 20-0235-10

  • DRM Relay-2 must be use for Mode/Factor Control. 

 

MODES/FACTORS

  • Mode 1 Card Only

  • Mode 2 Card + Pin

 

 

635-DRM Terminals (Function)

SCM Reader

LED    (LED control line)

LED Control

D 1    (Data 1)

D 1

VDC    (use separate p.s. for reader power)

VDC (to separate p.s.)

GND    (common Reader’s p.s. ground to Controller ground)

GND (common to controller ground)

D 0    (Data 0)

D 0

 

 

635-DRM’s RELAY-2 Terminals

SCM Mode/Factor

COM    (must tie to the reader’s power supply ground)

REL 2

NO    (to mode control line)

RELGRN 

 

 

NOTES:

  • Mode signal line = High (unconnected) for 2-Factor Card + Pin.

  • Mode signal line = Low (connected to ground) for 1-Factor Card Only, the

  • Place a schedule on Relay-2 in System Galaxy Reader Properties to alternate Mode/Factor.  

     

     

back to top

10.0 US GOV FICAM APL #

Contact Galaxy Control Systems for additional information.

 

Product

APL#

SUPPLIER

BridgePoint

10060

Galaxy Control Systems – PACS infrastructure

Veridt

10083

10084

Galaxy Control Systems – PACS infrastructure

Galaxy Control Systems – Validation System

HID

10097

10098

Galaxy Control Systems – PACS infrastructure

Galaxy Control Systems – Validation System

 

 

 

back to top

11.0 635-DRM (PN 20-0235-10) – READER PINOUT FULL SECTION

Each Reader section has the following terminals…

READER WIRING (9-PIN CONNECTOR)

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet. 

  • Reader may require separate power supply if the current draw is over 150 milliamps.

  • Ground the Drain-wire at one end only - at the DRM Board (GND).

  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

     

Reader Connector

PINS

635-DRM Terminals (Function)

Wiegand

ABA

9

LED    (LED control line)

LED Control

LED Control

8

D 1    (Data 1)

DATA 1

DATA

7

VDC    +12 VDC  (For +5VDC use Regulator PN 92-3001-05)

VDC

VDC

6

GND    (Power Supply Ground )

GND

GND

5

D 0     (Data 0)

DATA 0

CLOCK

4

unused

 

 

 

DOOR CONTACT & REX MOTION DETECT (9-PIN CONNECTOR)

  • 2-conductor, 22 AWG, overall shielded (for Door Contact). 

  • 4-conductor, 22 AWG; overall shielded (for REX/Motion Detector). for Door Contact

  • Separate Power Supply for REX/Motion Sensor.

  • Ground all Drain-wires at one end only (at the DRM Board "GND").

  • Refer to device manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

     

Reader Connector

PINS

635-DRM Terminals (Function)

Device State

3

COM    (Common)

LED Control

2

CNT    (Door Contact)

NC Normally Closed Contact = Door Closed/Contact Closed

1

REX    Request to Exit (motion sensor)

NO Normally Closed Open = Momentary Push Button

 

LOCK RELAY CONNECTOR (RLY-1)

  • 2-conductor, Minimum 18 AWG for LOCK (Manufacturer’s specs for wire gauge may supersede Galaxy’s instructions). 

  • Separate Power Supply required for Lock – follow manufacturer’s requirements for lock power supply.

  • Relay is Form-C SPDT Dry, (Rated max. 24v, 1.5 Amps)

     

635-DRM RELAY-1

LOCK DEVICE

COM

Land the lock wiring

NC = Normally Closed

according to the

NO = Normally Open

Manufacturer’s instructions.

 

RELAY-2 CONNECTOR – OPTIONAL OUTPUT 

  • For optional output (i.e. piezo, bell, buzzer)

  • Relay is Form-C SPDT Dry, (Rated max. 24v, 1.5 Amps)

  • Relay-2 (mode/timers/event-triggers) must be configured for desired behavior in SG Reader Properties

     

635 DRM RELAY-2

DEVICE

 

MODES *

Available Events (vary by Mode selected)

COM

Land wiring according

 

  • FOLLOWS

¨ Door Forced Open

¨ Valid Unlock

NC = Normally Closed

to Manufacturer’s

 

  • TIMED

¨ Door Open Too Long

¨ Duress

NO = Normally Open

instructions

 

  • SCHEDULED

¨ Invalid Access Attempt

¨ Passback

 

 

 

  • LATCHED

 

 

 

 

 

* set timers appropriately for desired behavior

 

 

 

back to top

12.0 DOOR & READER WIRING BLOCK DIAGRAM

 

This diagram shows the Lock, Door Contacts, REX and Reader connected to the controller. -

 

Connection Type

Max Distance

Wire Gauge & Specifications

Request to Exit

500 ft. from controller

22 AWG; 4-conductor, overall shielded; wired normally open (NO)

Door Contact

500 ft. from controller

22 AWG; 2-conductor, overall shielded; wired normally closed (NC)

Lock Hardware

500 ft. from controller

18 AWG; 2-conductor minimum, shielded; Separate Power Supply.

Refer to manufacturer’s instructions for device wiring (manufacturer's specs may supersede Galaxy specs).

 

 

Door Wiring Diagram

 

Jumper-out the following contacts, only if they are unused …

  1. DRM board: If door contacts are not installed, you must jumper CNT to GND.

  2. CPU board: If Low Battery wiring is not installed, you must jumper Low Batt to GND.

  3. CPU board: If AC Fail wiring is not installed, you must jumper the AC Fail to GND.

back to top